Existing Joint Check

 

 

 

Check the beam-column joints capacity for existing building as per NTC2018 (Circolare)

 

 

 

From the Main Menu select Design > Design Result > Existing Joint Check

 

 

 

From 'Set Existing Joint Check Parameter' Dialog, select the load combinations/Show elements type/ Check position for which joint capacity check will be calculated.

 

Refer to Usage of Table Tool and check the following data:

 

                                                

                                          

 Existing Joint Check Parameters dialog box

 

Load Cases/Combinations

 

Select the desired load combination or All Combinations.

 

Existing Joint Check Table Type

 

Select the elements either showing the selected elements or all elements

 

Select Check Position

   

    Set the check position of beam-column joint

 

 

 

Existing Joint Check Tables

 

 

Element : Element number

 

Position : Output position to existing beam-column joint check (Top or Bottom)

 

Stress : Kinds of stress, Tensile stress and compressive

 

Load : Govern Load combinations for joint stress ratio

 

Demand : Demand stress, Tensile stress and compressive stress as per equations C8.7.2.11/12 Circolare NTC2018

 

Capacity : Capacity stress, Tensile stress and compressive stress as per equations C8.7.2.11/12 Circolare NTC2018

 

Remark : If the 'Demand/Capacity' exceeds 1.0, 'NG' is printed, otherwise 'OK' is printed.

 

Note. Use Tips
1) This check option is activated only with NTC2018 codes.

2) If 'Apply Special Provision for Seismic Design' of concrete design code is active, this check option can't be activated.

3) This check must be performed only for 'Not Confined Joint' as defined in 7.4.4.3 of the NTC2018 codes.